EATON V-CG-SE 4-400W Monitoring device emergency power
 EATON V-CG-SE 4-400W Monitoring device emergency power

Safety Instructions

  • The module V-CG-SE shall only be used for its intended purpose and in undamaged and perfect condition!
  • When working on the electronic device make sure that it is disconnected from the voltage! Pay attention to the different power supplies in mains or battery operation.
  • Observe the national safety rules and regulations for prevention of accidents as well as the safety instructions included in these operating instruction marked with.

Conformity with  standards

Conforming to: EN 61 347-2-11 and EN 60 669-2-1.
Used for installation in luminaires of emergency lighting acc. to
EN 60 598-2-22 and for connection to safety lighting systems acc. to
DIN VDE 0100-718, EN 50 172 an DIN VDE V 0108-100-1.
Developed, manufactured and tested acc. to ISO 9001.

Technical data

  • Input voltage: 220-240 V, 50/60Hz 176 – 275 V DC
  • Standby power
  • loss (230V/50Hz): < 0.5W
  • Power consumption of connected lamp: 4 – 400W
  • max. cable length module-luminaire: 50 m
  • Usable into luminaires of the insulation class 1 and 2
  • Degree of protection: IP20
  • Perm. ambient temperature ta: -20 °C .. +60 °C
  • Test point temperature tc: 75°C
  • Connecting Push In
  • terminals: 0.13…1.5 mm²
  • Material of flame-resistant
  • the housing: polycarbonate
  • Weight: 0.040 kg
  • Dimensions
  • (L x W x H): 110 x 30 x 21mm
    Average design life = 50,000 h (ta /tc max. and a failure rate of ≤ 0.2% per 1,000h)
  • L‘ N: 220-240V, 50Hz
  • Switching threshold acc. EN 60598-2-22

Description/ Scope of application

The electronic monitoring module V-CG-SE is suitable for operation with electronic ballasts and incandescent lamps in combination with a CEAG safety lighting system with single luminaire monitoring in DCoperation (Cewa-Guard-technology) or AC-operation (S+ technology) for programmable switching in the final circuit (STAR-technology).

Not suitable for final circuits without STAR-technology

Installation

For the mounting and operation of electrical apparatus, the respective national safety regulations as well as the general rules of engineering will have to be observed.

Mounting

The location of mounting has to be in accordance with the respective instructions of the luminaire manufacturer.
Inadmissible temperatures during operation at the mounting location must be observed!
Statements regarding electromagnetic compatibility for a built-in situation are only possible with the respective luminaire. Instructions of the luminaire-or electronic ballast manufacturer must be observed.
We recommend the following guidelines:

  • Keep mains leads inside the luminaire as short as possible
  • Do not run mains leads adjacent to the electronic ballast or the lamp
  • Mains leads should be kept apart from lamp leads (ideally 5-10 cm distance)
    The mains connection has to be set to terminals L(U) and N(0), for luminaire connections terminals A1 – A2 have to be used (Fig 1 or 2).
    Fig 1 Connection to final circuits with S+ or STAR technology
    Connection instruction
    Fig 2 Connection to final circuits with S+ or STAR technology
    Connection instruction

    A slide-switch is used for pres election of connected load. The limit for ok/not ok depends on the setting of the switch:
Slide switch I OK î n.OK
ON >47mA <28mA
OFF >16mA <10mA

The limit în.OK is given as a peak current.
If the electronic ballast has a lamp failure the cut-off must be realized within 1.6 sec. The current consumption of ballast must be sinusoidal for AT-S+ systems or must comply with DIN EN 61000-3-2, clause 7.3a.).
The connection to the light switch of the general lighting will be done with terminals L’ – N (Fig 1 or 2).

Addressing
Before initial operation with CEAG safety lighting systems, the addressing of the individual luminaires has to be set. For this, the desired address is set on the address switches by means of a suitable screw driver. If the luminaire should not be monitored the code 0/0 has to be selected.

The increased functions „switchable operation“ and „operation mode“ will be available only by CEAG safety lighting systems with STAR-technology. (for this see the corresponding operating instructions of the system)
Addressing

(Address switch 1) (Address switch 2) Luminaire address
0 0 …….
0 1 1
0 2 2
……. ……. …….
1 1 11
……. ……. …….
2 0 20

Table 1

Table 2:

L (U) /N (0)  Address STAR Befehl / command L´/ N A1 / A2
0 V 0 – 20 0 / 230V AC 0 V
         
230 V AC
230 V AC
1 – 20
1 – 20
AUS / OFF AUS / OFF 0 V
230 V AC
0 V
230 V AC
230 V AC 1 – 20 EIN / ON 0 V 230 V AC
230 V AC 1 – 20 EIN / ON 230 V AC 230 V AC
230 V AC 1 – 20 Notbetrieb/Emergency 0 / 230V AC 230 V AC
220 V DC 0 – 20 0 / 230V AC 220 V DC

Table 3:

L (U) /N (0) 0 V Address 0 – 20 STAR Befehl / command L´/ N 0 / 230V AC A1 / A2 0 V
230 V AC
230 V AC
230 V AC
1 – 20
1 – 20
1 – 20
AUS / OFF AUS / OFF EIN / ON 0 V
230 V AC
0 V
230 V AC
0 V
230 V AC
230 V AC 1 – 20 EIN / ON 230 V AC 230 V AC
230 V AC 1 – 20 Notbetrieb/Emergency 0 / 230V AC 230 V AC
220 V DC 0 – 20 0 / 230V AC 220 V DC

STAR Befehl / command:
STAR command of the system to a V-CG-SE with a defined address

Dimensions

Dimensions

Mode of operation

The V-CG-SE contains a separate control input (L´/ N) for common switching of the mains and the safety lighting with a switch on location parallel to a remote switching (via STAR command).
The output voltage at A1 – A2 will be set depending to the voltage mode at L´ – N. The energy of A1 – A2 is only generated by the CEAG system.

Warning icon Attention:
Only for systems / switching over units with STAR – Technology suitable!!!
The module can be used in two modes.

A = L´ – N (positive logic)
Connection according Fig. 1
Use the tens at the address range
A = L´ – N acc. Fig. 3

A ≠ L´ – N (inverted logic)
Connection according Fig. 2
Use the tens at the address range
A ≠ L´ – N acc. Fig. 4

Programming at a system with STAR– Technology:

  • program the circuit to “via luminaire setup”
  • program the used address of the V-CG-SE to “non maintained mode” in the luminaire setup.

We reserve the right to make technical alterations without notice!

Support

Eaton
EMEA Headquarters
Route de la Longeraie 7
1110 Morges, Switzerland
Eaton.eu

CEAG Notlichtsysteme GmbH
Senator-Schwartz-Ring 26
59494 Soest, Germany
Tel.: +49 (0) 2921 69-870
Fax: +49 (0) 2921 69-617
E-Mail: info-n@eaton.com
Web: www.eaton.com

© 2021 Eaton
Publikations-Nr. IL451039ML
Bestell-Nr. 40071860160 (C)
Gültig ab Juni 2021

 

Documents / Resources

EATON V-CG-SE 4-400W Monitoring device emergency power [pdf]
V-CG-SE 4-400W Monitoring device emergency power, V-CG-SE 4-400W, Monitoring device emergency power, emergency power

References

Leave a comment

Your email address will not be published. Required fields are marked *